Wire gauge by amps and length
RV Wire Gauge by Current and Run Length
Pick the current and the one-way run length. Each page gives the conductor size for both the 3 percent and 10 percent voltage drop limits, how it changes with distance, and the fuse that belongs with it.
36 pages in this section.
-
10A at 5 ft
Carrying 10 amps over a 5 foot 12V run needs 14 AWG copper to stay within a 3 percent voltage drop. Ampacity, voltage drop and fus
-
10A at 10 ft
Carrying 10 amps over a 10 foot 12V run needs 10 AWG copper to stay within a 3 percent voltage drop. Ampacity, voltage drop and fu
-
10A at 15 ft
Carrying 10 amps over a 15 foot 12V run needs 8 AWG copper to stay within a 3 percent voltage drop. Ampacity, voltage drop and fus
-
10A at 25 ft
Carrying 10 amps over a 25 foot 12V run needs 6 AWG copper to stay within a 3 percent voltage drop. Ampacity, voltage drop and fus
-
20A at 5 ft
Carrying 20 amps over a 5 foot 12V run needs 10 AWG copper to stay within a 3 percent voltage drop. Ampacity, voltage drop and fus
-
20A at 10 ft
Carrying 20 amps over a 10 foot 12V run needs 8 AWG copper to stay within a 3 percent voltage drop. Ampacity, voltage drop and fus
-
20A at 15 ft
Carrying 20 amps over a 15 foot 12V run needs 6 AWG copper to stay within a 3 percent voltage drop. Ampacity, voltage drop and fus
-
20A at 25 ft
Carrying 20 amps over a 25 foot 12V run needs 4 AWG copper to stay within a 3 percent voltage drop. Ampacity, voltage drop and fus
-
30A at 5 ft
Carrying 30 amps over a 5 foot 12V run needs 8 AWG copper to stay within a 3 percent voltage drop. Ampacity, voltage drop and fuse
-
30A at 10 ft
Carrying 30 amps over a 10 foot 12V run needs 6 AWG copper to stay within a 3 percent voltage drop. Ampacity, voltage drop and fus
-
30A at 15 ft
Carrying 30 amps over a 15 foot 12V run needs 4 AWG copper to stay within a 3 percent voltage drop. Ampacity, voltage drop and fus
-
30A at 25 ft
Carrying 30 amps over a 25 foot 12V run needs 2 AWG copper to stay within a 3 percent voltage drop. Ampacity, voltage drop and fus
-
40A at 5 ft
Carrying 40 amps over a 5 foot 12V run needs 8 AWG copper to stay within a 3 percent voltage drop. Ampacity, voltage drop and fuse
-
40A at 10 ft
Carrying 40 amps over a 10 foot 12V run needs 4 AWG copper to stay within a 3 percent voltage drop. Ampacity, voltage drop and fus
-
40A at 15 ft
Carrying 40 amps over a 15 foot 12V run needs 2 AWG copper to stay within a 3 percent voltage drop. Ampacity, voltage drop and fus
-
40A at 25 ft
Carrying 40 amps over a 25 foot 12V run needs 1 AWG copper to stay within a 3 percent voltage drop. Ampacity, voltage drop and fus
-
50A at 5 ft
Carrying 50 amps over a 5 foot 12V run needs 6 AWG copper to stay within a 3 percent voltage drop. Ampacity, voltage drop and fuse
-
50A at 10 ft
Carrying 50 amps over a 10 foot 12V run needs 4 AWG copper to stay within a 3 percent voltage drop. Ampacity, voltage drop and fus
-
50A at 15 ft
Carrying 50 amps over a 15 foot 12V run needs 2 AWG copper to stay within a 3 percent voltage drop. Ampacity, voltage drop and fus
-
50A at 25 ft
Carrying 50 amps over a 25 foot 12V run needs 1/0 AWG copper to stay within a 3 percent voltage drop. Ampacity, voltage drop and f
-
60A at 5 ft
Carrying 60 amps over a 5 foot 12V run needs 6 AWG copper to stay within a 3 percent voltage drop. Ampacity, voltage drop and fuse
-
60A at 10 ft
Carrying 60 amps over a 10 foot 12V run needs 2 AWG copper to stay within a 3 percent voltage drop. Ampacity, voltage drop and fus
-
60A at 15 ft
Carrying 60 amps over a 15 foot 12V run needs 2 AWG copper to stay within a 3 percent voltage drop. Ampacity, voltage drop and fus
-
60A at 25 ft
Carrying 60 amps over a 25 foot 12V run needs 2/0 AWG copper to stay within a 3 percent voltage drop. Ampacity, voltage drop and f
-
80A at 5 ft
Carrying 80 amps over a 5 foot 12V run needs 4 AWG copper to stay within a 3 percent voltage drop. Ampacity, voltage drop and fuse
-
80A at 10 ft
Carrying 80 amps over a 10 foot 12V run needs 2 AWG copper to stay within a 3 percent voltage drop. Ampacity, voltage drop and fus
-
80A at 15 ft
Carrying 80 amps over a 15 foot 12V run needs 1/0 AWG copper to stay within a 3 percent voltage drop. Ampacity, voltage drop and f
-
80A at 25 ft
Carrying 80 amps over a 25 foot 12V run needs 3/0 AWG copper to stay within a 3 percent voltage drop. Ampacity, voltage drop and f
-
100A at 5 ft
Carrying 100 amps over a 5 foot 12V run needs 4 AWG copper to stay within a 3 percent voltage drop. Ampacity, voltage drop and fus
-
100A at 10 ft
Carrying 100 amps over a 10 foot 12V run needs 1 AWG copper to stay within a 3 percent voltage drop. Ampacity, voltage drop and fu
-
100A at 15 ft
Carrying 100 amps over a 15 foot 12V run needs 2/0 AWG copper to stay within a 3 percent voltage drop. Ampacity, voltage drop and
-
100A at 25 ft
Carrying 100 amps over a 25 foot 12V run needs 4/0 AWG copper to stay within a 3 percent voltage drop. Ampacity, voltage drop and
-
150A at 5 ft
Carrying 150 amps over a 5 foot 12V run needs 2 AWG copper to stay within a 3 percent voltage drop. Ampacity, voltage drop and fus
-
150A at 10 ft
Carrying 150 amps over a 10 foot 12V run needs 2/0 AWG copper to stay within a 3 percent voltage drop. Ampacity, voltage drop and
-
150A at 15 ft
Carrying 150 amps over a 15 foot 12V run needs 3/0 AWG copper to stay within a 3 percent voltage drop. Ampacity, voltage drop and
-
150A at 25 ft
Carrying 150 amps over a 25 foot 12V run needs more than 4/0 copper to stay within a 3 percent voltage drop. Ampacity, voltage dro